Networking Interface
(1) 100/10 MbE port for network connection
(2) GbE ports for surge in/out
Power
(1) OVC II AC in: NEMA 5‑15P, 1.8 m (5.9 ft) non-removable power cord
(4) Battery backup/surge protection: NEMA 5‑15R
(4) Surge protection: NEMA 5‑15R
Input Voltage Range
89—145V AC
Power Method
(1) TN system, 120V AC, 12A Max., 50/60 Hz
Nominal Input Voltage
120V AC
Frequency Range
AC mode: 50/60 Hz ±5 Hz (Auto sensing)
Battery mode: 60 Hz ±1 Hz
AC Voltage Regulation
±10% (Battery mode)
Transfer Time
6 ms typical; 10 ms max. (Battery mode)
Wave Form
Simulated sine wave (Battery mode)
Battery Type
(2) Lead Acid 12V, 9Ah
Runtime
Full load: 2.3 min
Half load: 8 min
Battery Charging Time
6-8 hours recovery to 90% capacity
Overload at On-Line Mode
110% 5 min go to fault
120% go to fault immediately
Overload at Battery Mode
110% shutdown in 5 sec
120% shutdown immediately
Short Circuit Protection at On-Line Mode
Breaker, 250V AC, 15A
Output Short-Circuit Current
Ipeak 348.0A
Irms 115.1A
Buttons
(1) Power
(1) Factory reset
LEDs
Off: device not turned on
Flashing white: initializing / factory default
Steady white: waiting for adoption
Steady blue: device adoption and working
Flashing blue: battery mode
Alternating white/blue: firmware upgrading
Rapid flashing blue: locate
Steady red: warning
Flashing red: low battery
Operating Altitude
3,000 m (1.9 mi)
Operating Environment
Pollution Degree 2
Ambient Storage Temperature
-20 to 50° C (-4 to 122° F)
Ambient Operating Temperature
0 to 40° C (32 to 104° F)
Ambient Operating Humidity
0 to 95% noncondensing
Certifications
FCC, IC, UL 1778, CSA C22.2 No. 107.3