Networking Interface
(1) 100/10 MbE port for network connection
(2) GbE ports for surge in/out
Power
(1) OVC II AC in: NEMA 5‑20P
(8) Battery backup/surge protection: NEMA 5‑20R Power Method
(1) TN system, 120V AC, 16A Max., 50/60 Hz
Frequency Range
AC mode: 50/60 Hz ±5 Hz (Auto sensing)
Battery mode: 60 Hz ±1 Hz
Transfer Time
6 ms typical; 10 ms max. (Battery mode)
Wave Form
Pure sine wave (Battery mode)
Runtime
Full load: 9 min
Half load: 22 min
Battery Charging Time
8 hours recovery to 90% capacity
Overload at On-Line Mode
103–120% 5 min go to fault
120–150% 10 sec go to fault
150% 1 sec go to fault
Overload at Battery Mode
103–120% 1 min go to fault
120–150% 10 sec go to fault
150% 0.5 sec go to fault
Short Circuit Protection at On-Line Mode
Emergency Power Off (EPO)
Buttons
(1) Power
(1) Factory reset
(1) Circuit breaker
LEDs
Off: device not turned on
Flashing white: initializing / factory default
Steady white: waiting for adoption
Steady blue: device adoption and working
Flashing blue: battery mode
Alternating white/blue: firmware upgrading
Rapid flashing blue: locate
Steady red: warning
Flashing red: low battery
Ambient Storage Temperature
-15 to 50° C (5 to 122° F)
Ambient Operating Temperature
0 to 40° C (32 to 104° F)
Ambient Operating Humidity
Certifications
FCC, IC, UL 1778, CSA C22.2 No. 107.3