Gate Hub
Gate Hub

UA-Hub-Gate

Datasheet
In The Box
Marketing Images
Installation Guide
Gate Hub
Gate Hub
Gate Hub
Dimensions
175 x 126 x 26 mm (6.9 x 5 x 1")
Supported Doors
1 gate, 1 side door
Input Terminals
(1) Gate exit request (1) Gate position (1) Side door exit (1) Side door position (1) Emergency
Power Method
PoE++ UL 294 Power-limited Class 2 PSU UL 60950-1/62368-1 LPS/PS2 PSU
Weight
460 g (1 lb)
Enclosure Material
Polycarbonate
Mounting
DIN-rail (Included)
Indoor and Outdoor Use
Indoor only: device itself Outdoor: with waterproof junction box
Ambient Operating Temperature
-30 to 60° C (-22 to 104° F)
Ambient Operating Humidity
5 to 90% noncondensing
Networking Interface
(5) 10/100/1000 Base-T
PoE Interface
(1) PoE++ input, 50V DC, 1A (4) PoE outputs, 50V DC, Max. 28W
Max. Power Consumption
22W (Without PoE output) 50W (With PoE output)
Digital Input
Gate exit request, gate position, side door exit request, side door position, emergency
Dry Output Relay
(2) Operator: rated 30V DC, up to 1A (1) Aux: rated 30V DC, up to 1A
Powered Output Relay
Side door lock: 12V DC, up to 1A
LEDs
Buttons
(1) Factory-reset
Recommend Max. Cable Length
UA-Lock-Electric (400mA)
24 AWG length: 25 m (82 ft) 22 AWG length: 42 m (138 ft) 20 AWG length: 66 m (217 ft) 18 UACC-Cable-DoorLockRelay length: 100 m (328 ft)
UA-Lock-Magnetic-540kg (500mA)
24 AWG length: 20 m (66 ft) 22 AWG length: 32 m (105 ft) 20 AWG length: 51 m (167 ft) 18 UACC-Cable-DoorLockRelay length: 80 m (262 ft)
UA-Lock-Magnetic-270kg (800mA)
24 AWG length: 12 m (29 ft) 22 AWG length: 20 m (66 ft) 20 AWG length: 30 m (98 ft) 18 UACC-Cable-DoorLockRelay length: 46 m (151 ft)
Other locks (1A)
24 AWG length: 9 m (30 ft) 22 AWG length: 15 m (49 ft) 20 AWG length: 24 m (79 ft) 18 UACC-Cable-DoorLockRelay length: 36 m (118 ft)
PoE Cabling Requirements
Cat 5e cabling is the minimum performance category recommended. The performance category utilized should match the transmission speed required at the installation site. The minimal conductor gauge permitted to connect between the PSE or power injector and the PD shall be 26 AWG (0.13 mm² ) for patch cords; 24 AWG (0.21 mm² ) for horizontal or riser cable.
UL 294 Level
Destructive attack: Level I Line security: Level I Endurance: Level I Standby power: Level I
UL 294 Statement
Compliance with IEEE 802.3 specifications was not verified as part of UL 294. The equipment is intended to comply with the section of the National Electrical Code, ANSI/NFPA 70, Article 725.121, Power Sources for Class 2 and Class 3 Circuits.
CAN/ULC-60839-11-1 Grade
Grade assignment: I
Certifications
CE, FCC, IC, UL 294, CAN/ULC-60839-11-1
Document number, and issue date and/or revision level
UA-Hub-Gate, V01
Management Application
Access
Software Information
The software version can be checked at https://unifi.ui.com